Customer:
Quasar Engineering / The Neste Rotterdam MNA Expansion Project
Task & Solution:
As part of the electrical inspection activities at refinery substations in Rotterdam, we performed electrical safety measurements on power outlets and incoming power supply lines to electrical cabinets to verify correct installation and safe operation.
The inspections included testing Residual Current Devices (RCDs) to verify their trip current and disconnection time, as well as measuring voltage and line impedance at power outlets and incoming cabinet supply lines upstream of the RCDs. All measurements were performed using a Fluke 1664 Installation Multifunction Tester to assess electrical supply conditions and verify the effectiveness of protective devices. Following the inspections, we prepared detailed reports documenting the measurements, test results, and condition of each installation.
The inspections and measurements were carried out in accordance with the applicable requirements of the Dutch NEN 1010 standard, supporting the verification of electrical safety and the reliable operation of the substation installations.